Lighting Load Control Solution
 
Light source type Unit power Maximum number of lamps and maximum power output of single-phase circuit
Control Power Factor Compensation BCH8 Contactor
Capacitor capacity 16A 25A 40A 63A
Common incandescent lamp, low pressure halogen lamp
Replacement of mercury lamp (ballastless)
40W 38 1550W 57 2300W 115 4600W 172 6900W
60W 30 reach
45 reach
85 reach
125 reach
75W 25 2000W 38 2850W 70 5250W 100 7500W
100W 19 28 50 73
150W 12 18 35 50
200W 10 14 26 37
300W 7 2100W 10 3000W 18 5500W 25 7500W
500W 4 6 10 reach
15 reach
1000W 2 3 6 6000W 8 8000W
1500W 1 2 4 5
Electronic Low Voltage 12V or 24V Halogen Lamp
Distribution inductance transformer 20W 15 300W 23 450W 42 850W 63 1250W
50W 10 reach
15 27 reach
42 reach
75W 8 600W 12 23 1950W 35 2850W
100W 6 8 18 27
Distribution Electronic Transformer 20W 62 1250W 90 1850W 182 3650W 275 5500W
50W 25 reach
39 reach
76 reach
114 reach
75W 20 1600W 28 2250W 53 4200W 78 6000W
100W 16 22 42 60
Fluorescent lamp with inductance ballast of starter
Single tube 15W 22 330W 30 450W 70 1050W 100 1500W
No Compensation (1)18W 22 reach
30 reach
70 reach
100 reach
20W 22 850W 30 1200W 70 2400W 100 3850W
36W 20 28 60 90
40W 20 28 60 90
58W 13 17 35 56
65W 13 17 35 56
80W 10 15 30 48
115W 7 10 20 32
Single tube 15W 5μF 15 200W 20 300W 40 600W 60 900W
Parallel Compensation (2)
18W 5μF 15 reach
20 reach
40 reach
60 reach
20W 5μF 15 800W 20 1200W 40 2400W 60 3500W
36W 5μF 15 20 40 60
40W 5μF 15 20 40 60
58W 7μF 10 15 30 43
65W 7μF 10 15 30 43
80W 7μF 10 15 30 43
115W 16μF 5 7 14 20
2 or 4 tube 2×18W 30 1100W 46 1650W 80 2900W 123 4450W
Series Compensation
4×18W 16 reach
24 reach
44 reach
68 reach
2×36W 16 1500W 24 2400W 44 3800W 68 5900W
2×58W 10 16 27 42
2×65W 10 16 27 42
2×80W 9 13 22 34
2×115W 6 10 16 25
Fluorescent Lamp for Distribution Electronic Ballast
1 tube or 2tobe 18W 74 1300W 111 2000W 222 4000W 333 6000W
36W 38 reach
58 reach
117 reach
176 reach
58W 25 1400W 37 2200W 74 4400W 111 6600W
2×18W 36 55 111 166
2×36W 20 30 60 90
2×58W 12 19 38 57
Compact fluorescent lamp
Matching external5W 210 1050W 330 1650W 670 3350W Untested
Electronic ballast 7W 150 reach
222 reach
478 reach
9W 122 1300W 194 2000W 383 4000W
11W 104 163 327
18W 66 105 216
26W 50 76 153
Equipped with integrated electronic ballast 5W 160 800W 230 1150W 470 2350W 710 3550W
(Replacing incandescent lamps) 7W 114 reach
164 reach
335 reach
514 reach
9W 94 900W 133 1300W 266 2600W 411 3950W
11W 78 109 222 340
18W 48 69 138 213
26W 34 50 100 151
High Voltage Mercury Lamp without Trigger for Distribution Inductance Ballast to Replace High Voltage Sodium Lamp for Distribution Inductance Ballast and Trigger
No Compensation (1) 50W 15 750W 20 1000W 34 1700W 53 2650W
80W 10 reach
15 reach
27 reach
40 reach
125/110W(3) 8 1000W 10 1600W 20 2800W 28 4200W
250/220W(3) 4 6 10 15
400/350W(3) 2 4 6 10
700W 1 2 4 6
Parallel Compensation (2) 50W 7μF 10 500W 15 750W 28 1400W 43 2150W
80W 8μF 9 reach
13 reach
25 reach
38 reach
125/110W(3) 10μF 9 1400W 10 1600W 20 3500W 30 5000W
250/220W(3) 18μF 4 6 11 17
400/350W(3) 25μF 3 4 8 12
700W 40μF 2 2 5 7
1000W 60μF 0 1 3 5
Low Voltage Sodium Lamp with Distribution Inductance Ballast and External Trigger
No Compensation (1)
35W 5 270W 9 320W 14 500W 24 850W
55W 5 reach
9 reach
14 reach
24 reach
90W 3 360W 6 720W 9 1100W 19 1800W
135W 2 4 6 10
180W 2 4 6 10
Parallel Compensation (2)
35W 20μF 3 100W 5 175W 10 350W 15 550W
55W 20μF 3 reach
5 reach
10 reach
15 reach
90W 26μF 2 180W 4 360W 8 720W 11 1100W
135W 40μF 1 2 5 7
180W 45μF 1 2 4 6
High pressure sodium lamp, metal halide lamp
Distribution inductance ballast and 35W 16 600W 24 850W 42 1450W 64 2250W
External trigger 70W 8 12 reach
20 reach
32 reach
No Compensation (1)150W 4 7 1200W 13 2000W 18 3200W
250W 2 4 8 11
400W 1 3 5 8
1000W 0 1 2 3
Distribution inductance ballast and 35W 6μF 12 450W 18 650W 31 1100W 50 1750W
External trigger, 70W 12μF 6 reach
9 reach
16 reach
25 reach
Parallel Compensation (2)
150W 20μF 4 1000W 6 2000W 10 4000W 15 6000W
250W 32μF 3 4 7 10
400W 45μF 2 3 5 7
1000W 60μF 1 2 3 5
2000W 85μF 0 1 2 3
Distribution electronic ballast 35W 24 850W 38 1350W 68 2400W 102 3600W
70W 18 reach
29 reach
51 reach
76 reach
150W 9 1350W 14 2200W 26 4000W 40 6000W
(1) The uncompensated inductive ballast circuit consumes twice the output current of each set of lamps, so it is seldom used. 
(2) The total capacitance of shunt power factor compensation capacitors limits the number of lamps controlled by a contactor. The rated power is the limit value of the total capacitance of the standard contactor lower circuit of 16A, 25A, 40A and 63A, and the corresponding values that cannot be exceeded are 75, 100, 200 and 300 uF. If the capacitance value is different from the value in the table, it is allowed to calculate the maximum number of connected lamps according to the capacitance limit value.
(3) High-pressure mercury lamps with 120W, 250W and 400W power without triggers will gradually replace high-pressure sodium lamps with 10W, 220W and 350W corresponding power with triggers.